Performance data
Water flow rates and throw distances for monitors (water guns)
For all units – equipped with MZ-nozzles – the throw distance can be shortened up to 20% of the indicated throw distance by changing from full jet to spray jet. The indicated figures are valid only when calm.
| 8 bar | 10 bar | 8 bar | 10 bar | 8 bar | 10 bar | |||
| HH1260 | ||||||||
| MZ 1200 | 25,5 | 1180 | 1300 | 50 | 55 | 35 | 38 | 25° / 90° |
| MZ 1500 | 28 | 1400 | 1650 | 55 | 64 | 38 | 45 | 25° / 90° |
| Waterring monitors | ||||||||
| Nozzle | 30 | 1430 | 1610 | 52 | 58 | 36 | 40 | 30° / 90° 1) |
| MZ 1200 | 25,5 | 1140 | 1270 | 48 | 53 | 34 | 37 | 30° / 90° 1) |
| MZ 1500 | 27,5 | 1300 | 1550 | 51 | 60 | 35 | 42 | 30° / 90° 1) |
| HR 362 | ||||||||
| Nozzle | ||||||||
| MZ 1200 | 25,5 | 1200 | 1340 | 50 | 55 | 35 | 38 | 30° / 60° 2) |
| MZ 1600 | 30 | 1600 | 1800 | 55 | 61 | 39 | 43 | 30° / 60° 2) |
| HH 365 | ||||||||
| Nozzle | 30 | 1600 | 1800 | 60 | 67 | 42 | 47 | 30° / 90° |
| MZ 1600 | 30 | 1600 | 1800 | 55 | 61 | 39 | 43 | 30° / 90° |
| HR 366 | ||||||||
| Düse | 40 | 3000 | 3300 | 67 | 72 | 46 | 50 | 30° / 90° |
| MZ 4000 | 48 | 4200 | 4700 | 70 | 78 | 49 | 55 | 30° / 90° |
| HR 567 | ||||||||
| Nozzle | 26 | 1200 | 1350 | 53 | 58 | 37 | 41 | 35° / 90° 3) |
| 30 | 1600 | 1800 | 60 | 67 | 42 | 47 | 35° / 90° 3) | |
| 42 | 3200 | 3600 | 65 | 70 | 46 | 49 | 35° / 90° 3) | |
| MZ 4000 | 48 | 4200 | 4700 | 70 | 78 | 49 | 55 | 35° / 90° 3) |
1) |
80° style with pressure gauge. |
2) |
Unlocked -10° / +60°. |
3) |
Unlocked -15° / +90°. |